4 zones fire control panel FS4000
Features:
- Fire alarm lines:
- Maximum number of fire detectors in a line - 32
- Connecting line - two wire
- Maximum resistance of a line - 100 ohm
- Current thresholds for:
- Fault condition - 0-3mA
- Duty mode - 3-12 mA
- Fire condition - 12-80mA
- Short circuit - >80mA
- Controllable outputs for fire condition:
- Number - 2 pcs;
- Type - potential, relay with independent control
- Electrical characteristics - (19-28)V DC/1 A
- Relay outputs for fire condition:
- Number - 2 pcs
- Type - potential-free, switching with independent control
- Electrical characteristics - 3А/125V AC, 3A/30V DC
- Relay output for fault condition:
- Number - 1 pcs
- Type - potential-free, switching with independent control
- Electrical characteristics - 3А/125V AC, 3A/30V DC
- Performance:
- Control over fire alarm lines and controllable outputs for fault conditions (short circuit and interruption) and automatic reset.
- Detection of removed fire detector and automatic reset.
- Identification of manual call points.
- LED indication for alarm state and emergency.
- Delay of outputs for fire condition with time period of 1, 2, 3, 4, 5, 6 or 7 minutes after fire condition is registered.
- Option for ''LOGICAL AND '' realization of two fire alarm lines.
- Duty Mode condition with direct activation of Fire Condition 2nd Stage '' for two fire alarm lines.
- Status Indication of the device for data transmission RS485.
- Option for switching on/off interface RS485 communication.
- Built-in sounder for fire condition – one tonal, continuous, can be switched off.
- Built-in sounder for fault condition – one tonal, discontinuous, can be switched off.
- Test mode for fire alarm lines.
- Disabling fire alarm lines.
- Disabling outputs for fire condition.
- Expanding the options by means of extra relay outputs for fire condition for each line for operation in a local network.
- Indications of registered events:
- Light indication - LED
- Sound - Built-in sounder
- Power supply
- Mains:
Voltage - (187-252)V AC
Frequency - 50/60 Hz
- Backup batteries:
Battery type - lead, gel electrolyte
Number of batteries - 2 pcs
Nominal voltage of the backup battery - 12V
Nominal capacity C20 - (4,5) Ah
Charge voltage - 28V DC
Operation in Duty mode upon interruption in main power supply:
98 h (24V / 4,5Ah),
24 h (24V / 1,2Ah)
- Power supply to external devices:
- Voltage - (19-28)V DC
- Maximum current value (including current of contr.outputs) - 1,2A
- Dimension - 313х218х85 mm
- Weight (backup batteries not included) - 1,5 kg