4 zones fire control panel FS4000 

Features:

  • Fire alarm lines:

          - Maximum number of fire detectors in a line - 32

          - Connecting line - two wire

          - Maximum resistance of a line - 100 ohm

  • Current thresholds for:

          - Fault condition - 0-3mA

          - Duty mode - 3-12 mA

          - Fire condition - 12-80mA

          - Short circuit - >80mA

  • Controllable outputs for fire condition:

          - Number - 2 pcs;

          - Type - potential, relay with independent control

          - Electrical characteristics - (19-28)V DC/1 A

  • Relay outputs for fire condition:

          - Number - 2 pcs

          - Type - potential-free, switching with independent control

          - Electrical characteristics - 3А/125V AC, 3A/30V DC

  • Relay output for fault condition:

          - Number - 1 pcs

         - Type - potential-free, switching with independent control

         - Electrical characteristics - 3А/125V AC, 3A/30V DC

  • Performance:

      - Control over fire alarm lines and controllable outputs for fault conditions (short circuit and interruption) and automatic reset.

         -    Detection of removed fire detector and automatic reset.

         -    Identification of manual call points.

         -    LED indication for alarm state and emergency.

         -    Delay of outputs for fire condition with time period of 1, 2, 3, 4, 5, 6  or 7 minutes after fire condition is registered.

         -    Option for ''LOGICAL AND '' realization of two fire alarm lines.

         -    Duty Mode condition with direct activation of Fire Condition 2nd Stage '' for two fire alarm lines.

         -    Status Indication of the device for data transmission RS485.

         -    Option for switching  on/off  interface RS485 communication.

         -    Built-in sounder for fire condition – one tonal, continuous, can be switched off.

         -    Built-in sounder for fault condition – one tonal, discontinuous, can be switched off.

         -    Test mode for fire alarm lines.

         -    Disabling fire alarm lines.

         -    Disabling outputs for fire condition.

         -    Expanding the options by means of extra relay outputs for fire condition for each line for operation in a local network.

  • Indications of registered events:

         - Light indication - LED

         - Sound - Built-in sounder

  • Power supply

         - Mains:

            Voltage - (187-252)V AC

            Frequency - 50/60 Hz

         - Backup batteries:

            Battery type - lead, gel electrolyte

             Number of batteries - 2 pcs

             Nominal voltage of the backup battery - 12V

             Nominal capacity C20 - (4,5) Ah

             Charge voltage - 28V DC

             Operation in Duty mode upon interruption in main power supply:

             98 h (24V / 4,5Ah),

             24 h (24V / 1,2Ah)

  •    Power supply to external devices:

          - Voltage - (19-28)V DC

          - Maximum current value (including current of contr.outputs) - 1,2A

  • Dimension - 313х218х85  mm
  • Weight (backup batteries not included) - 1,5 kg