2-4 cilpu adrešu panelis
Features:
- Microprocessor control unit with 2 loop lines expandable to 4
- Possibility of managing up to 128 points for loop (512 max).
- Point self-learning and point logic address.
- Backlit graphic display 240*128 - 4.7 “.
- Event log: 1000 events
- Chronological history directly shown on display.
- 10 passwords programmable on 3 levels.
- 480 programmable zones, 240 Group of Zone, 240 Group of Device
- USB port for local PC connection for programming via SW
- Possibility of monitoring detector signal/noise ratio level
- Real time clock with built-in buffer battery
- Non volatile memory
- Control unit outputs: 5 (alarm, siren, failure, programmable (mains failure/exclusion)
- Internal buzzer
- Programmable alarm threshold: for zone, for individual point
- Exclusion of individual point /zone
- Power supply: 230Vac
- Max. current: 1.5A@24Vdc
- Battery charge limit and battery charge check
- Battery housing: two 12 @12Vdc batteries
- Possibility of implementing 2 Km loop with 2 x 1.5 mm cable (shielded)
- Noise immunity up to 30Vm
- Common dialogue protocol for all system control units
- Dimensions: 490 (L) x 350 (H) x 145 (D) mm
- COMPLIANT WITH EN54 STANDARDS, part 2 and part 4