J408-8
Features:
EN54 and EN12094-1 approved (with J400-EXT extinguishment module)8 (J408-8) controlled, balanced, bypassable input zonesUp to 32 devices can be connected to each zone: conventional fire detectors, alarm buttons, gas detectorsGas zone compatible with 4 – 20 mA gas detectorsManual call point recognitionProgrammable thresholdsMissing detectorsDay/Night modeAlarm verification timeProgrammable restoral and reset timesOne alarm-repeat output (open collector) for each input zone2 supervised, silenceable, bypassable 24 V alarm output for the activation of piezoelectric sirens, fire bells and flashersSilenceable, bypassable alarm output, for the activation of 24 V self-powered sirensSilenceable fault-warning output for the activation of signalling and auxiliary devicesSupervised fire output for telephone dialler activationProgrammable open-collector outputAlarm/fault memory up to next resetCommand for silencing sirensKeypad commands require key or codeProgrammable from PC or keypad50 events log viewed via PCRS485 bus for connecting up to 4 repeater panelsPower supply: 230 Vac ±10%27.6 Vdc 1.5 A switching supply/battery-chargerCompartment for two 12 V 7 Ah batteriesDimensions (wxhxd): 354x280x100 mmWeight (without batteries): max. 4 Kg